What Happens When LEV Fails Its Test? Labels, Repairs And Retesting
When an LEV hood or system fails its thorough examination and test, the employer still has a legal duty under COSHH to keep it working properly, and HSE’s guidance sets out a clear sequence: the failure is flagged on the spot, the employer receives a short written description of what is wrong and what to do, the system is repaired, and a competent person checks it before it is relied on again. This guide covers each step, including the labels HSE recommends and the airflow checks that help catch a failing system between tests.
Need a first test, or a retest after repairs? A short list of the extraction and the site address, sent to info@gsbinspections.co.uk, lets us price it; we aim to reply within 48 hours.
The COSHH Duty Behind Every LEV Test
Regulation 9 of the Control of Substances Hazardous to Health Regulations 2002 requires engineering controls such as LEV to be maintained in an efficient state, in efficient working order, in good repair and in a clean condition. LEV plant must be thoroughly examined and tested at least once every 14 months, or more often for the processes listed in Schedule 4. Each examination and test, and every repair it leads to, has to be recorded, and the record or a summary kept available for five years or more.
A failed test is therefore not the end of the matter: the duty to maintain the system in efficient working order continues, and the repair itself becomes part of the record.
LEV Test Labels: What HSE Recommends
HSE is clear that there is no specific legal requirement on employers or examiners to label LEV. It explains why labels are still recommended: the employer, supervisors and operators need to know whether an examination has been done, when the next one is due and, critically, when a hood or system has failed.
HSE’s guidance recommends that examiners label each hood with a test record. The label can instead sit nearby, for example close to the system’s on-off switch, as long as supervisors and operators can see it clearly.
Red Failed Labels On LEV Hoods And Systems
HSE recommends that a red Failed label goes on any hood or system that has failed, to warn supervisors and operators directly. The examiner can attach it with the employer’s agreement, or issue it to the employer’s responsible person. With the label should come a short emergency written report giving a clear description of what is wrong and a list of practical remedial actions.
Labels are not the only option. HSE accepts other means, as long as it is clear to the employer and to operators that the equipment needs rapid attention.
Repairing And Rechecking LEV After A Failed Test
Once the employer has had the hood or system repaired, HSE says a competent person needs to check that it is effective and adequately controls exposure; the Failed label can then be removed. The repair, and the check that followed it, belong in the COSHH regulation 9 record alongside the original examination and test.
In our view the most useful repair brief is the examiner’s own readings: knowing which hood fell short, and by how much, lets the contractor target the cause rather than guess.
Airflow Indicators: Catching LEV Problems Between Tests
HSE notes that one of the main reasons LEV stops working is a fall in airflow, from material building up or ducting being damaged. There is no specific legal requirement for airflow indicators, but HSE says you should have some way of checking that adequate airflow is maintained, and its guidance HSG258 recommends indicators. HSE describes an airflow indicator as currently the only method that shows the operator or supervisor immediately if there is a problem.
For a simple system of fan, filter, duct and hood, HSE says a manometer measuring static pressure across the filter can give sufficient indication. Paper or plastic tell-tales hung in the airflow are, in HSE’s words, not effective in all but very simple systems extracting low-hazard substances.
Who Should Test, Repair And Recheck LEV
HSE says people who supply, examine and maintain LEV all need to be competent, meaning the right mix of skills, knowledge and experience, and suggests asking about qualifications, training, experience and previous work. It also advises getting more than one quote. Keeping the test separate from the repair, by using a tester who does not install or service extraction, means the pass or fail is not tied to who is paid for the work.
Failed LEV Test Questions
Is it a legal requirement to label LEV after a test?
No. HSE says there is no specific legal requirement to label LEV, but its guidance recommends a test record label on each hood and a red Failed label on any hood or system that fails.
Who puts the Failed label on?
HSE says the examiner can attach it with the employer’s agreement, or issue it to the employer’s responsible person, along with a short written report of what is wrong.
When can a Failed label come off?
Once the hood or system has been repaired and a competent person has checked that it is effective and adequately controls exposure, according to HSE.
Do we have to fit airflow indicators?
There is no specific legal requirement, but HSE says you should have some way of checking that adequate airflow is maintained, and its guidance HSG258 recommends airflow indicators.
Independent LEV Testing And Retesting From GSB
GSB carries out LEV examination and testing under COSHH regulation 9. We do not design, supply, install or maintain extraction, so a failed result is never a route to selling you the repair.
Email your list of systems, what each extracts and the site address to info@gsbinspections.co.uk, and our aim is a price within 48 hours. Got a failed report you want explained? Call 01782 855481; the phone is answered by GSB’s two directors, the owners and both senior engineers. As an associate member of SAFed, GSB follows the federation’s code of practice for inspection bodies.